Task
The state volume converter UNIGAS PTZ
converts the measured gas volume Vb of one gas meter at operation condition
into m³ dry gas from standard condition pn = 1,01325 bar and Tn = 273,15
K.
The compressibility is considered as fixed value or according to the chart
pressure stored in the calculator and temperature dependent.
Operating principle
The operation volume gas meter transmits
impulses proportional to the measured flow to the processor of the UNIGAS PTZ
Compact by means of a low frequency impulse converter mounted in or at the gas
meter. The processor receives the values of the operation pressure and
temperature from the sensors, which are either installed directly at the gas
meter or at the piping.
Scope of delivery
UNIGAS PTZ Compact consists of the
micro-processor controlled computing device, the pressure and the temperature
sensors and an optimised 3-way test cock. The computing device can be mounted
directly onto the gas meter or separately and is certified for use in hazardous
aereas according to EEX ib IIC T5.
Pressure ranges
Pabs= 0,9 bar to 6,0 bar with
official calibration "national" Pabs= 4,0 bar to 10,0 bar with
official calibration "national"
Temperature ranges
Gas temperatures -10°C to
40°C Ambient temperature -10°C to 40°C Storage temperatures
-20°C to 50°C
Gas types
Natural gas acc. to DVGW-worksheet G 260,
technical gases. |